What size boiler for a 3-bedroom house? (UK: 28-34 kW combi, 18-26 kW system)

A 3-bedroom house needs 28-34 kW from a combi boiler or 18-26 kW from a system boiler with one or two bathrooms, on the UK installers' tables. A third bathroom moves it to 35-42 kW combi or 27-40 kW system. The heating alone is smaller: a 90 m² house loses 7.20 kW to 11.70 kW depending on insulation. The combi figure is higher because it heats the hot water on demand. Below: the kW by bathrooms, by radiator count and by floor area.

Open the boiler size calculator

1. 3-bedroom house: combi and system kW by bathrooms

The installers' tables (Heatable, What Size Boiler Do I Need?, combi boiler sizing for typical UK homes) read the row from bedrooms and bathrooms and take the higher of the two. Three bedrooms select the middle row, so one or two bathrooms give the same answer.

Table 1: boiler kW for a 3-bedroom house by bathrooms, UK installers' tables
BathroomsCombiSystem or regular
1 bathroom28-34 kW18-26 kW
2 bathrooms28-34 kW18-26 kW
3 bathrooms35-42 kW27-40 kW

A 4-bedroom house sits in the same row; the 4-bedroom boiler guide covers what changes above it.

2. By number of radiators

The same tables have a radiator column (Heatable, What Size Boiler Do I Need?, radiator column of both tables): up to 10 radiators in the first row, 10 to 20 in the second, 20 or more in the third. With one bathroom, the radiator count alone gives the rows below. Three bedrooms still select the 28-34 kW row, so a low radiator count does not take a 3-bed house below it on the tables; 20 or more radiators take it above.

Table 2: boiler kW by radiator count with one bathroom, and the manufacturer's single combi output
RadiatorsCombi rowSystem rowCombi by count
624-27 kW12-18 kW24 kW
824-27 kW12-18 kW24 kW
1028-34 kW18-26 kW28 kW
1228-34 kW18-26 kW28 kW
1528-34 kW18-26 kW32 kW
1828-34 kW18-26 kW32 kW
2035-42 kW27-40 kWbeyond the guide
2535-42 kW27-40 kWbeyond the guide

The last column is the manufacturer's guide (Ideal Heating, Combi Boiler Size Guide, radiators a combi output serves). More on one output: how many radiators a 28 kW boiler can run. To size each radiator, use the radiator size guide.

3. Heat loss of a 3-bedroom house by floor area

Bedrooms do not tell you the floor area, and the heating load follows the floor area: floor area x 130 W/m² poor, 100 W/m² average, 80 W/m² good (TradeCalculator.co.uk, Radiator Sizing Calculator, rule of thumb for whole-building heat loss per m² of floor area). Find your floor area in the table.

Table 3: heat loss in kW by floor area and insulation
Floor areapooraveragegood
50 m²6.50 kW5.00 kW4.00 kW
70 m²9.10 kW7.00 kW5.60 kW
90 m²11.70 kW9.00 kW7.20 kW
120 m²15.60 kW12.00 kW9.60 kW
150 m²19.50 kW15.00 kW12.00 kW
200 m²26.00 kW20.00 kW16.00 kW

Every row is below the 28-34 kW combi range, which is why the combi figure is set by the hot water. A system boiler (18-26 kW) sits closer to the heating load. The combi boiler size calculator puts your floor area, bedrooms, bathrooms and radiators side by side; a Gas Safe installer's heat loss calculation decides.

Frequently asked questions

What size combi boiler for a 3-bed house?
28-34 kW with one or two bathrooms (Heatable, What Size Boiler Do I Need?, combi boiler sizing for typical UK homes). The tables put 3 and 4 bedrooms in the same row, so a 3-bed house with a family bathroom and an en-suite is still 28-34 kW; a third bathroom moves it to 35-42 kW.
Is a 24 kW combi big enough for a 3-bedroom house?
Not on the installers' tables: 24-27 kW is the row for one or two bedrooms with one bathroom, and a 3-bed house starts at 28-34 kW. The manufacturer's radiator guide puts a 24 kW combi at up to 10 radiators (Ideal Heating, Combi Boiler Size Guide, radiators a combi output serves), so the radiator count alone would allow one in a house with few radiators; the bedrooms row does not. The installer's heat loss and hot water check decide.
Combi or system boiler for a 3-bed house?
Both are on the tables: 28-34 kW combi, which heats water on demand with no cylinder, or 18-26 kW system or regular, which heats a hot water cylinder. The sources suggest considering a system boiler at the top row (three or more bathrooms, 20+ radiators), where a 3-bed house with three bathrooms sits: 35-42 kW combi against 27-40 kW system.
How many kW does it take to heat a 3-bedroom house?
Floor area x 80 W/m² to 130 W/m² depending on insulation (TradeCalculator.co.uk, Radiator Sizing Calculator, rule of thumb for whole-building heat loss per m² of floor area). A 90 m² house: 7.20 kW well insulated, 9.00 kW average, 11.70 kW poorly insulated. Table 3 has other floor areas; measure yours rather than guessing it from the bedrooms.
What size boiler for a 3-bed house with 2 bathrooms?
28-34 kW combi or 18-26 kW system: the same row as one bathroom, because 3 bedrooms already select it (Heatable, What Size Boiler Do I Need?, combi boiler sizing for typical UK homes).

Last updated 2026-09-29. Sizing estimates from published charts and rules of thumb (ENERGY STAR, manufacturer guides), each with its source and date: a Manual J load calculation by an installer is the final word.